A model number of the furnace would be helpful too.
Furnace control board has no power.
Don t forget when the blower door is open.
First make sure you have power to the board.
With the stat in off mode.
If your building s electrical system supports 120 volts your furnace needs a transformer to convert to the correct voltage to run the controls ignition and timers.
Just went thru the flow charts from rheem on that furnace.
If your electric furnace is blowing a fuse repeatedly when turning on your first step should be to call in an experienced hvac repair professional.
Power up transformer cool mode works blower stays on after temp is reached.
Furnace control board fuse keeps blowing 1 answers hi i have a carrier furnace 48gs 036090311tp with a honeywell t8401c thermostat.
What would cause electric furnace circuit board to fail.
Check for 24 volts to board from transformer.
Changed control board in gas furnace new board has no power to transformer blower motor lead on cool terminal hot all the time all the safety switches ohm out.
The sequence is like this.
I can run the fan on continuously but when i put the heat to on on the t stat the 5 amp fuse on the control board lh33wp003a in the furnace blows.
In some cases this will be line voltage and in other cases the board will get its power from the control transformer.
If you have 24 volts and no light on board.
It is possible that the problem could stem from your electrical system rather than the furnace itself but your hvac system is the best place to start.
Measure from r to c at the control board.
Measure from r to w.
You should see 24vac.
The electric furnace transformer may be failing causing the system to short.
Heat mode goes strait to trouble code bad ground open ignition circuit also no power from board to induction motor.
You should see 24vac.
Either way check to make sure you have the proper input voltage to the board.
Fan only operation is running.
If so it will need to be replaced.
The ac power is disconnected.